Mr. Heater MH80CV Operations Instructions Page 3

  • Download
  • Add to my manuals
  • Print
  • Page
    / 12
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 2
3
Operating Instructions and Owner’s ManualMr. Heater | Convection Construction Heater
OPERATING PRECAUTIONS
This is a propane, direct-fired, convection heater. It's intended
use is primarily temporary heating of buildings under
construction, alteration or repair.
Propane is heavier than air. If propane leaks from a connection
or fitting, it sinks to the floor, collecting there with the
surrounding air, forming a potentially explosive mixture.
Obviously, propane leaks should be avoided, so set up the
propane supply with utmost care. Read enclosed Odor Fade and
Propane Sheet for additional information about detecting
propane leaks. Leak check new connections or reconnections
with a soap and water solution and follow all connection
instructions herein. Also, ask your propane dealer for advice on
the propane application and supply installation and ask him to
check it if there are any questions.
This heater was designed and certified for use as a construction
heater in accordance with ANSI Standard Z83.7/CGA 2.14-2000.
Check with your local fire safety authority if you have any
questions about your applications. Other standards govern the
use of fuel gases and heat producting products in specific
applications. Your local authority can advise you about these.
Direct-Fired means that all of the combustion products enter the
heated space. Even though this heater operates very close to 100
percent combustion efficiency, it still produces small amounts of
carbon monoxide. Carbon monoxide (called CO) is toxic. We can
tolerate small amounts but not a lot. CO can build up in a heated
space and failure to provide adequate ventilation could result in
death. The symptoms of inadequate ventilation are:
headache
dizziness
burning eyes and nose
nausea
dry mouth or sore throat
So, be sure to follow advice about ventilation in these operating
instructions.
When the heater is to be operated in the presence of other
people the user is responsible for properly acquainting
those present with the safety precautions and instructions,
and of the hazards involved.
SAFETY PRECAUTIONS
1. Check the heater thoroughly for damage. DO NOT operate a
damaged heater.
2. DO NOT modify the heater or operate a heater which has
been modified from its original condition.
3. DO NOT light or operate heater unless the shells are fully
extended and locked into position. See enclosed assembly
sheet for instructions.
4. Use only propane gas.
5. Use only VAPOR WITHDRAWAL propane supply. If there is
any question about vapor withdrawal, ask your propane
dealer.
6. Mount the propane cylinders vertically (shutoff valve up).
Secure them from falling or being knocked over and protect
them from damage.
7. Locate propane containers at least (USA) 7 ft. (2.13m) for
MH80CV and 9 ft. (2.7m) for MH200CV (Canada)10 ft. (3m)
from the heater and do not direct exhaust toward
containers.
8. IMPORTANT Use only the hose and regulator assembly
provided with the heater. Match the color stripe on the
hangtag attached to the hose assembly with the color on the
label located near the propane inlet fitting on the heater.
Inspect hose assembly before each use of the heater. If there
is excessive abrasion or wear, or hose is cut, replace with
hose assembly listed on parts list before using heater.
9. For indoor use only. Area must be well ventilated. Figure 1.
(also see "Operating Precautions").
10. If at any time gas odor is detected, IMMEDIATELY
DISCONTINUE operation until the source of gas has been
located and corrected. Read enclosed Odor fade and
Propane Sheet for additional information about detecting
propane leaks.
11. Install the heater such that it is not directly exposed to water
spray, rain and/or dripping water.
12. Maintain minimum clearance from normal combustible
material (like paper). Figure 2.
13. Due to the high surface and exhaust temperatures, adults
and children must observe clearances to avoid burns or
clothing ignition.
14. Operate only on a stable, level surface.
15. Do not use with duct work. Do not restrict inlet or exit.
16. Do not move, handle or service while hot or burning.
17. Use only in accordance with local codes or, in the absence of
local codes, with the Standard for the Storage and Handling
of Liquefied Petroleum Gases ANSI/NFPA 58 and CSA
B149.1, Natural Gas and Propane Installation Code.
Figure 1
VENTILATION: Minimum openings required
Opening Opening
Heater near floor near ceiling
Convection MH80CV, MH200CV ..... 2 ft
2
..............................
2 ft
2
Figure 2
MINIMUM CLEARANCE: From normal combustible material
MH80CV, MH200CV
Clearance Convection
From sides .................................................. 4 ft
From top .................................................... 6 ft
Locate 10' from canvas or plastic tarpaulins or similar coverings
and secure them to prevent flapping or movement due to wind
action.
Page view 2
1 2 3 4 5 6 7 8 ... 11 12

Comments to this Manuals

No comments