Mr. Heater Plaque HSVFR10LP Operations Instructions Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 14
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
5
Installation Instructions and Owner’s Manual
Unvented Natural Gas Fired Room Heater
attics* and crawl spaces. Follow the National Fuel Gas
Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for Com-
bustion and Ventilation for required size of ventilation
grills or ducts.
*IMPORTANT: Do not provide openings for inlet or
outlet into attic. If attic has a thermostat-controlled
power vent, heated air entering the attic will activate
the power vent.
IMPORTANT: Vent-free heaters add moisture to
the air. Although this is benecial, installing heater
in rooms without enough ventilation air may cause
mildew to form from too much moisture. See Fresh
Air for Combustion and Ventilation, pages 4
through 6.
INSTALLATION
NOTICE: This heater is intended for the use as supple-
mental heat. Use this heater along with your primary
heating system. Do not install this heater as your pri-
mary heat source. If you have a central heating system,
you may run system’s circulating blower while using
heater. This will help circulate the heat throughout the
house. In the event of a power outage, you can use this
heater as your primary heat source for the duration of
the outage.
heater, Gas furnace, Vented gas heater, Gas re-
place logs, and Other gas appliances*
*Do not include direct-vent gas appliances. Direct-
vent draws combustion air from the outdoors and
vents to the outdoors.
Example:
Gas water heater 40,000 Btu/hr
Vent Free Heater + 20,000 Btu/hr
Total =60,000 Btu/hr
4. Compare the maximum Btu/hr the space can support
with the actual amount of Btu/hr used.
Example: 51,800 Btu/hr (maximum Btu/hr the
space can support)
60,000 Btu/hr (Actual amount of Btu/hr used)
The space in the above example is a conned
space because the actual Btu/hr used is more than
the maximum Btu/hr the space can support.
You must provide additional fresh air. Your options
are as follows:
A. Rework worksheet, and the space of an adjoining
room. If the extra space provides an unconned
space, remove door to adjoining room or add venti-
lation grills between the rooms. See Ventilation Air
From Inside Building (Fig. 2)
B. Vent room directly to the outdoors. See Ventilation
Air From Outdoors (Fig. 3).
C. Install a lower Btu/hr heater if lower Btu/hr size
makes room unconned.
If actual Btu/hr used is less than the maximum Btu/
hr the space can support, the space is an uncon-
ned space. You will need no additional fresh air
ventilation.
VENTILATION AIR
Ventilation from Inside Building
This fresh air would come from an adjoining unconned
space. When ventilation to an adjoining unconned
space, you must provide two permanent openings: one
within 12” of the ceiling and one within 12” of the oor
on the wall connecting the two spaces (see options 1
& 2 of gure 2). You can also remove door into adjoin-
ing room (see option3, g 2). Follow the National Fuel
Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, Air for
Combustion and Ventilation for required size of ventila-
tion grills or ducts.
WARNING: Rework worksheet, adding the space
of the adjoining unconned space. The combined
space must have enough fresh air to supply all ap-
pliance in both spaces.
Ventilation from Outdoors
If necessary provide extra fresh air by using ventila-
tion grills or ducts. Connect these items directly to the
outdoors or spaces open to the outdoors. These include
Ventilation
Gills into
Adjoining
Room - Op-
tion 1
Ventilation Gills into Ad-
joining Room - Option 2
12”
12”
Or remove
door into
Adjoining
Room -
Option 3
INLET
AIR
OUTLET
AIR
VENTILATION CRAWL SPACE
TO CRAWL
SPACE
TO ATTIC
VENTILATION AIR
VENTILATED
ATTIC
OUTLET AIR
Figure 2
Figure 3.
Page view 4
1 2 3 4 5 6 7 8 9 10 ... 13 14

Comments to this Manuals

No comments